Susol MCCB में FMU, FTU और ATU के बारे में बताएं।

FTU : Thermal over protection (1In Fixed)


          Magnetic short-circuit protection (10In Fixed)


FMU : Thermal over protection (0.8~1In Adjustable)


          Magnetic short-circuit protection (10In Fixed)


ATU : Thermal over protection (0.8~1In Adjustable)


          Magnetic short-circuit protection (5~10In Adjustable)